Table 4: Full Load Motor Nominal Currents in Amperes Corresponding to 60Hz AC Horsepower Ratings

HP
110-120V : 1Ø
110-120V : 3Ø
220-240V : 1Ø
220-240V : 3Ø
440-480V : 1Ø
440-480V : 3Ø
550-600V : 1Ø
550-600V : 13Ø
1/45.8-2.9-----
1/37.2-3.6-----
1/29.84.04.92.02.51.02.00.8
3/413.85.66.92.83.51.42.81.1
116.07.28.03.64.01.83.21.4
1.520.010.410.05.25.02.64.02.1
224.013.612.06.86.03.44.82.7
334.019.217.09.68.54.86.83.9
556.030.428.015.214.07.611.26.1
7.580.044.040.022.021.011.016.09.0
10100.056.050.028.026.014.020.011.0
15135.084.068.042.034.021.027.017.0
20-108.088.054.044.027.035.022.0
25-136.0110.068.055.034.044.027.0
30-160.0136.080.068.040.054.032.0
40-208.0176.0104.088.052.070.041.0
50-260.0216.0130.0108.065.086.052.0
60---154.0-77.0-62.0
75---192.0-96.0-77.0
100---248.0-124.0-99.0
125---312.0-156.0-125.0
150---360.0-180.0-144.0
200---480.0-240.0-192.0

Note: The information in the above table was derived from Table 18 in CSA standard C22.2 # 14, Tables 44 and 45 in CSA standard C22.1 Part 1 and Tables 430-138 and 430-149 in the 1993 National Electrical Code Handbook.  This table is for reference only and complete information should be obtained from the appropriate agency.